1 Functions
※ LED/LCD display interface
※ Leakage alarm function
※ Temperature alarm function
※ Sound and light alarm function
※ Alarm record query
※ Fire protection DC24V linkage
※ Alarm passive switch signal output
※ Circuit breaker tripping automatic/manual optional
2 Technical parameters
※※Working voltage: AC220±10%
※Leakage alarm value: 100~999mA continuously adjustable
※Temperature alarm value: 55~120℃ continuously adjustable
※Alarm channel: 1~8 leakage/4 temperature
※Output trip: AC220V active signal
※Fire linkage: DC24V input
※Alarm output: Passive switch
※Alarm mode: Sound and light alarm
※Alarm sound pressure: ≥70dB/m
※Communication mode: Type A 485 communication/Type B C two-bus communication
※Communication line quality: ZR-RVS-2x1.5mm² twisted pair
※Communication distance: ≤1500m
※Use environment: -20℃~60℃
※Relative humidity: ≤90%RH(40℃±2℃)
※Altitude: ≤4500m
※Equipment size: 128Lx90Wx55H
※Installation method: Guide rail installation
※Implementation standard: GB14287.2-2014
3 Product Dimensions (Type A)
Electrical fire monitoring system
Note 1: Type A, Type B and Type C are three independent electrical fire monitoring systems. The controller and host are not compatible with each other.
Note 2: Type A: 485 communication Type B: two-wire (two-bus) communication Type C: economical two-wire communication
Note 3: Only the model number needs to be noted for selection. If you need information on type BC, please refer to the manual