مصنوعات کی تفصیلات
عمومی سوالات
مصنوعات کی تفصیلات

1 Functions

 

※ LED/LCD display interface

※ Leakage alarm function

※ Temperature alarm function

※ Sound and light alarm function

※ Alarm record query

 

※ Fire protection DC24V linkage

※ Alarm passive switch signal output

※ Circuit breaker tripping automatic/manual optional

 

2 Technical parameters

Working voltage: AC220±10%

※Leakage alarm value: 100~999mA continuously adjustable

※Temperature alarm value: 55~120℃ continuously adjustable

※Alarm channel: 1~8 leakage/4 temperature

※Output trip: AC220V active signal

※Fire linkage: DC24V input

※Alarm output: Passive switch

※Alarm mode: Sound and light alarm

※Alarm sound pressure: ≥70dB/m

 

 

※Communication mode: Type A 485 communication/Type B C two-bus communication

※Communication line quality: ZR-RVS-2x1.5mm² twisted pair

※Communication distance: ≤1500m

※Use environment: -20℃~60℃

※Relative humidity: ≤90%RH(40℃±2℃)

※Altitude: ≤4500m

※Equipment size: 128Lx90Wx55H

※Installation method: Guide rail installation

※Implementation standard: GB14287.2-2014

 

3 Product Dimensions (Type A)

Electrical fire monitoring system

Note 1: Type A, Type B and Type C are three independent electrical fire monitoring systems. The controller and host are not compatible with each other.

Note 2: Type A: 485 communication Type B: two-wire (two-bus) communication Type C: economical two-wire communication

Note 3: Only the model number needs to be noted for selection. If you need information on type BC, please refer to the manual


رابطہ
اپنی معلومات چھوڑیں اور ہم آپ سے رابطہ کریں گے۔

ہمارے بارے میں

صارفین کی خدمات

ہم سے رابطہ کریں

ای میل: selina@powerboxoml.com

ٹیلی فون: +86-19050239506

وی چیٹ اور واٹس ایپ: 19050239506