產品細節
常問問題
商品介紹

1 Functions

 

※ LED/LCD display interface

※ Leakage alarm function

※ Temperature alarm function

※ Sound and light alarm function

※ Alarm record query

 

※ Fire protection DC24V linkage

※ Alarm passive switch signal output

※ Circuit breaker tripping automatic/manual optional

 

2 Technical parameters

Working voltage: AC220±10%

※Leakage alarm value: 100~999mA continuously adjustable

※Temperature alarm value: 55~120℃ continuously adjustable

※Alarm channel: 1~8 leakage/4 temperature

※Output trip: AC220V active signal

※Fire linkage: DC24V input

※Alarm output: Passive switch

※Alarm mode: Sound and light alarm

※Alarm sound pressure: ≥70dB/m

 

 

※Communication mode: Type A 485 communication/Type B C two-bus communication

※Communication line quality: ZR-RVS-2x1.5mm² twisted pair

※Communication distance: ≤1500m

※Use environment: -20℃~60℃

※Relative humidity: ≤90%RH(40℃±2℃)

※Altitude: ≤4500m

※Equipment size: 128Lx90Wx55H

※Installation method: Guide rail installation

※Implementation standard: GB14287.2-2014

 

3 Product Dimensions (Type A)

Electrical fire monitoring system

Note 1: Type A, Type B and Type C are three independent electrical fire monitoring systems. The controller and host are not compatible with each other.

Note 2: Type A: 485 communication Type B: two-wire (two-bus) communication Type C: economical two-wire communication

Note 3: Only the model number needs to be noted for selection. If you need information on type BC, please refer to the manual